Vetrix Multi-Function Display Unit Transmitter

Features

  • Measures Differential Pressure, Humidity and Temperature
  • Designed specifically for clean rooms
  • Designed for flush mount
  • 316L front panel, PMMA window, flat surface, no dust stay, good for all detergents, sanitizers and bactericides
  • Parallel or alternatively display input channels 1 to 3
  • Large high light 3.2” color TFT LCD display
  • Multiple inputs and outputs for different applications
  • High accuracy sensor, 100% field changeable
  • Optional 3 analog 4~20mA/0~10V inputs signals
  • Optional 3 analog 0~10V outputs signals
  • Optional RS485/Modbus RTU and key functions
  • Compatible to any DDC/PLC/SCADA or other data collect and control systems
  • Very high performance/price ratio: replace the single channel(T/RH/DP) display instruments, provide value added multi-function combination including local measurement, displaying and networking.
Enquiry

Vetrix Multi-function Display Unit Transmitter is the obvious choice wherever a high degree of cleanliness is vital, in addition to the precise measurement of differential pressure, humidity, and temperature. Vetrix Multi-function Display Unit Transmitter is used particularly in cleanrooms, hospitals, pharmaceutical, electronics, and wherever small variances in pressure are monitored. Every aspect of cleanroom monitoring is under your control! You can achieve reproducible conditions, stay flexible and also reduce your maintenance costs.

Specification

Display High light 3.2” color TFT LCD, resolution 320×240
Display Panel Material PMMA
Resolution ±0.1 engineering unit
Channels 1~3 channels, parallel (simultaneously) or single
row (alternate) display
Engineering Unit 3 preset units, °C/°F, %RH and Pa
Update Time <1s
Front Panel Material 316L stainless steel, 1.5mm thick
Back Housing Parts Fire-proof ABS+PC UL94 V-0 class
Protection Front panel IP65 (built-in temp. & humidity sensor
cap IP54)
Weight MINI: about 380g; Horizontal: about 450g; Vertical: about 650g
Power Supply 16~28VAC/16~35VDC
Consumption 0.5VA
Temperature Humidity Differential pressure
Range 0~50°C 0~100%RH 0~60Pa
Accuracy 0.4°C or 0.3°C
(@15~40°C)
3% or 2%RH
(@25°C,20~80%RH)
1% or 0.5%FS
Nonlinear / <0.1%RH /
Repeatability ±0.1°C ±0.1%RH /
Hysteresis / ±1.0%RH /
Long term drift <0.02°C/Year <0.25%RH/Year <0.5%FS/Year
Response time <90s
(in slow air)
<40s
(25°C, in slow air)
0.5~30s
Temp drift / / <0.05%FS/°C(zero)
<0.08%FS/°C(span)
Temp. comp. / / 0~50°C
Medium Temp. / / 0~60°C
Work Temp. / / 10xFS(over load)
15xFS(burst)

Download

Vetrix Multi Function Display Unit Transmitter_DpstarGroup

Reviews

There are no reviews yet.

Be the first to review “Vetrix Multi-Function Display Unit Transmitter”

Your email address will not be published. Required fields are marked *