ENVIRONMENTAL CONDITIONS |
Operating temperature |
-20°C to +60°C |
Storage temperature |
-20°C to +85°C |
Calibration temperature |
20…28°C |
Relative humidity |
< 95% RH (non-cond.) |
Protection degree |
IP20 |
Installation in |
Pollution degree 2 & meas. / overvoltage cat. II |
MECHANICAL SPECIFICATIONS |
Dimensions (HxWxD) |
109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ 4501/451x |
109 x 23.5 x 116 / 131 mm |
Weight approx. |
170 g |
Weight incl. 4501 / 451x (approx.) |
185 g / 200 g |
DIN rail type |
DIN EN 60715/35 mm |
Wire size |
0.13…2.08 mm2 AWG 26…14 stranded wire |
Screw terminal torque |
0.5 Nm |
Vibration |
IEC 60068-2-6 |
2…13.2 Hz |
±1 mm |
13.2…100 Hz |
±0.7 g |
COMMON SPECIFICATIONS |
Supply |
|
Supply voltage |
19.2…31.2 VDC |
Fuse |
1.25 A SB / 250 VAC |
Max. required power |
≤ 1.9 W / ≤ 3.1 W (1 / 2 ch.) – low current ≤ 2.5 W (1 ch.) – high current |
Max. power dissipation, 1 / 2 ch. |
≤ 1.1 W / ≤ 1.7 W – low current |
Max. power dissipation |
≤ 1.7 W (1 ch.) – high current |
Isolation voltage |
|
Test /working: Input to any |
2.6 kVAC / 300 VAC reinforced isolation |
Output 1 to output 2 |
1.5 kVAC / 150 VAC reinforced isolation |
Status relay to supply |
1.5 kVAC / 150 VAC reinforced isolation |
Programming |
PR 45xx |
EMC immunity influence |
< ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst |
< ±1% of span |
INPUT SPECIFICATIONS |
NPN and mechanical switch |
|
Trig level LOW |
≤ 2.0 VDC |
Trig level HIGH |
≥ 4.0 VDC |
Max. external voltage |
28 VDC |
Input impedance |
3.5 kΩ |
PNP |
|
Trig level LOW |
≤ 8.0 VDC |
Trig level HIGH |
≥ 10.0 VDC |
Max. external voltage |
28 VDC |
Input impedance |
3.5 kΩ |
OUTPUT SPECIFICATIONS |
Status relay |
|
Max. voltage |
125 VAC / 110 VDC |
Max. current |
0.5 AAC / 0.3 ADC |
Max. AC power |
62.5 VA / 32 W |
Output ripple |
< 40 mVRMS |
OBSERVED AUTHORITY REQUIREMENTS |
EMC |
2014/30/EU |
LVD |
2014/35/EU |
ATEX |
2014/34/EU |
RoHS |
2011/65/EU |
EAC |
TR-CU 020/2011 |
EAC Ex |
TR-CU 012/2011 |
APPROVALS |
ATEX |
KEMA 07ATEX0147 X |
IECEx |
KEM 09.0001X |
c FM us |
FM19US0057X / FM19CA0030X |
INMETRO |
DEKRA 16.0006 X |
c UL us, UL 61010-1 |
E314307 |
c UL us, UL 913 |
E233311 (only 9203xxxx-U9) |
EAC Ex |
RU C-DK.HA65.B.00355/19 |
DNV-GL Marine |
TAA00000JD |
ClassNK |
TA18527M |
SIL |
SIL 2 certified & fully assessed acc. to IEC 61508 |