MR13 Series is controller in 1 with input 3 points, setting 3 points, and output 3 points.
Digital Controller – Shimaden MR13 Series
Features
- 3-channel controller, 3-channel input, 3-channel setting and simultaneous 3-channel display are possible
- Accuracy: ± (0.3% FS + 1 digit)
- Follow-up type PV input function
- Follow-up type SV setting function
- Remote/local and DI input function
- Programmable 1 pattern with 9-step function
- Included a new processing system, Expert PID, remarkably improved PID control efficiency; overshoot and undershoot are controlled effectively.
- Interface RS232C/RS485
Specification
Display | |
LED display | PV display 7-segment LED green 4 digits 3 channels to be displayed individually. |
SV display 7-segment LED orange 4 digits | |
CH display 7-segment LED orange 1 digit | |
Action display LED | Control output display: 3-OUT1, OUT2, OUT3 |
Auto tuning | 1-AT |
Follow type SV display | 1-FLW Program RUN: 1-RUN |
Event output display | 3-EV1, EV2, EV3 |
Remote input display | 1-REM Communication display: 1-COM |
Display accuracy | ±(0.3%FS + 1 digit) Standard accuracy |
Temperature range in which accuracy is maintained | 23 °C±5 °C |
Display resolution | Depends on measuring range (0.001, 0.01, 0.1, 1) |
Sampling cycle | 0.5 seconds |
Measured value display range | -10% to 110% of measuring range |
Setting | |
Setting | By 6 front key operation |
Setting range | Same as measuring range |
Higher/lower limit setting limiter | Higher and lower limits to be set separately; free within measuring range (Lower limit < higher limit) |
Follow type SV setting | SV of CH2 or CH3 can be set to follow CH1 (deviation setting) (on condition that measuring range of CH2 or CH3 is the same as that of CH1.) |
Input | |
Input type has to be the same for 3 channels (measuring range can be selected individually). | |
Thermocouple | B, R, S, K, E, J, T, N, PL II, WRe5-26, {L, U (DIN43710)} |
(Multiple input, multiple range. Refer to measuring range code table.) | |
External resistance | 100Ω maximum |
Input impedance | 500kΩ minimum |
Burnout | Standard feature (up scale) |
Cold junction temperature compensation accuracy | ±2.0 °C (5–45 °C) |
R.T.D. | JIS Pt100/JPt100 3-wire type (Multiple range. Refer to measuring range code table.) |
Amperage | Approx. 0.25 mA |
Lead wire tolerable resistance | 5Ω maximum/wire |
Voltage | ±10, 0–10, 0–20, 0–50, 10–50, 0–100mV DC, or ±1, |
0–1, 0–2, 0–5, 1–5, 0–10V DC | |
(Multiple input, programmable range. Refer to measuring range code table.) | |
Input impedance | 500kΩ minimum |
Current | 4–20, 0–20mA DC |
(Multiple input, programmable range. Refer to measuring range code table.) | |
Receiving impedance | 250Ω |
Sampling cycle | 0.5 seconds |
PV bias | ±1999 digit |
PV filter | OFF, 1–100 seconds |
Follow type PV input | PV input of CH2 or CH3 can be set to follow CH1 (deviation setting) (on condition that measuring range of CH2 or CH3 is the same as that of CH1.) |
Isolation | Insulated between input and various outputs (not insulated between input and system, remote input and DI input) |
Control | |
Control mode | Expert PID control with auto tuning function |
Proportional band (P) | OFF, 0.1–999.9%FS (OFF=ON/OFF action) |
Integral time (I) | OFF, 1–6000s (OFF=P, PD action with manual reset) |
Derivative time (D) | OFF, 1–3600s (OFF=P, PI action) Manual reset: ±50.0% |
ON/OFF hysteresis | 1–999 digit |
Proportional cycle | 0.5–120.0 seconds (0.5 sec. is unit for setting.) |
Control output characteristics | RA/DA selectable (set to RA when shipped) |
Output limiter | Higher limit, lower limit 0.0–100.0% (lower limit < Higher limit) |
Soft start | OFF, ON (Fixed to 10 sec.; Valid when power is turned on, RTS RUN, and when returned from scaleover.) |
Control output/rating | |
Output specification has to be the same for 3 channels. | |
Contact output (Y) | 1a 240V AC 2.5A/resistive load |
Current output ( I ) | 4–20mA, 0–10mA DC/load resistance 600Ω maximum. |
SSR drive voltage output (P) | 15V±3V DC/ Load current 20mA maximum |
Voltage output (V) | 0–10V DC/Load current 2mA maximum |
Operation output updating cycle | 0.5 second |
Isolation | Insulated between control output and system and input (not insulated between control output I, P or V and analog output) |
Event output (optional) | |
Number of outputs | : 3 -EV1, EV2, EV3 (Selectable from CH1, CH2 and CH3, individual setting, individual output) |
Output rating | : Contact output 1a (common) 240V AC / 1A (resistive load) |
Setting | : Individual setting |
0) NON : Not assigned | |
1) DEV : Higher limit deviation value alarm | |
2) DEV : Lower limit deviation value alarm | |
3) DEV : Higher/lower limit value alarm in case SV is out of measuring range | |
4) DEV : Higher/lower limit value alarm in case SV is within measuring range | |
5) PV : Higher limit absolute value alarm | |
6) PV : Lower limit absolute value alarm | |
7) SO : ON upon scaleover | |
8) RUN : ON during program RUN | |
9) END : ON for 1 sec. upon termination of program | |
10) STEP : ON for 1 sec. upon termination of program step | |
Hysteresis | 1–999 digit (when DEV or PV has been selected) |
Standby action | Selectable (when DEV or PV has been selected) |
Action delay time | OFF, 1–9999 seconds (when DEV or PV has been selected) |
Isolation | Insulated between alarm output and various inputs/outputs and system |
Remote setting (optional, selectable between this function and DI) | |
Setting signal | 1–5V, 0–10V, 4–20mA |
Setting range | Same as measuring range |
Accuracy of setting | ±(0.3%FS+1) digit |
Channel for setting | Selectable from CH1, CH2 and CH3 |
Remote scaling | Within measuring range (inverted scaling possible) |
Remote bias | -1999–5000 digit |
Remote filter | OFF, 1–100 seconds |
Sampling time | 0.5 second |
Isolation | Insulated between remote input and various outputs (not insulated from system and various inputs) |
External control input (DI) (optional, selectable between this function and remote setting) | |
Number of input point | 1 |
Input rating | Non-voltage contact, open collector input (about 5V/0.4mA DC impress) |
Action type | NON, FLW (follow type SV), RST/ RUN, HLD and ADV |
Isolation | Insulated between DI input and various outputs (not insulated from system and various inputs) |
Program (optional) | |
Registrable pattern | 1 |
Number of steps | 9 maximum |
Program setting range | |
Level | Same as measuring range |
Time | 1–9999 minutes/step |
Ramp | To be set automatically according to level and time |
Number of executions | 9999 maximum |
PID output limiter | To be set selectively from 3 types of PID & output limiter |
External control input | DI/non-voltage 1 point (RUN/RST, HLD, ADV) |
Action status output | RUN, END and STEP to be selectively output to event output |
CH2 and CH3 in SV follow setting | Program to be executed by making CH2 or CH3 deviation-follow to pattern set in CH1 in SV follow |
setting. Not in SV follow setting, program is executed in FIX mode. | |
Additional functions | Temporary suspension (HLD), carry-forward (ADV), PV start |
Analog output (optional, selectable between this function and communication) | |
Number of output | 1 |
Output types | Selectable from CH1_PV, CH2_PV, CH3_PV, CH1_SV, CH2_SV, CH3_SV, CH1_OUT, CH2_OUT and CH3_OUT |
Output rating | 0–10mV DC/Output impedance 10Ω |
0–10V DC/Load current 1mA maximum | |
4–20mA DC/Load resistance 300Ω maximum | |
Output accuracy | ±0.3%FS (to displayed value) |
Output resolution | Approx. 1/8000 |
Output updating cycle | 0.5 seconds |
Output scaling | Within measuring range (inverted scaling possible |
Isolation | Insulated between analog output and various inputs and system (not insulated between analog output and control outputs I, P and V) |
Communication (optional, selectable between this function and analog output) | |
Communication type | RS-232C, RS-485 |
Communication system | Half duplex start-stop synchronous system |
Communication speed | 1200, 2400, 4800, 9600, 19200bps |
Data format | 7 bits, 8 bits, no parity, even parity selectable |
Communication address | 1–99 |
Communication code | ASCII code |
Communication protocol | Shimaden standard protocol |
Communication format | Control code selectable, BCC check arithmetic system selectable |
Isolation | Insulated between communication signal and system/input/output |
Others | Meets the EMC standards with an additional clamp filter (E04SR301334, SEIWA Information Systems Co.,LTD) |
Others | |
Data storage | By non-volatile memory (EEPROM) |
Ambient temperate/humidity ranges | -10–50 °C/below 90% RH (on condition that there is no dew condensation) |
Temperature for storage | Between-20 and 65 °C |
Power voltage | 100V–260V AC ±10% (50/60 Hz) |
Power consumption | 18VA maximum |
Input noise removal ratio | Normal mode 45 dB minimum (50/60 Hz) |
Common mode 140 dB minimum (50/60 Hz) | |
Applicable standard | RoHS: EN50581 |
Insulation resistance power terminal | Between input/output terminals |
500V DC 20MΩ minimum | |
Between input/output terminals and protective conductor terminal: 500V DC 20MΩ minimum | |
Dielectric strength | : 1 minute at 2300V AC between input/output terminals and power terminal (inductive current 5mA) 1 minute at 2300V AC between power terminal and ground terminal (inductive current 5mA) |
Protective structure | Dust and splash proof front panel equivalent to IP66 (applicable only when panel thickness is 1.2 to 3.2 mm) |
Material | PPE resin molding (equivalent to UL94V-1) |
External dimensions | 96 x 96 x 110 mm (Panel depth: 100 mm) |
Mounting | Push-in panel (one-touch mount) |
Panel cutout size | H92 x W92 mm |
Weight | Approx. 420 g |
Ordering Information
ITEMS | CODE | SPECIFICATIONS | ||||||||||||||
SERIES | MR13 – | MPU-Based 3 Channel Auto-Tuning PID Controller DIN 96 x 96mm | ||||||||||||||
INPUT | 1 | Thermocouple B, R, S, K, E, J, T, N, PLII, WRe5-26, U, L | Multi-input Multi-range |
|||||||||||||
2 | R.T.D. Pt100 / JPt100 | Multi-range | ||||||||||||||
3 | Voltage (mV) -10–10, 0–10, 0–20, 0–50, 10–50, 0–100mV DC | Multi-input Programmable Range |
||||||||||||||
4 | Current (mA) 0–20, 4–20mA DC | |||||||||||||||
6 | Voltage (V) -1–1, 0–1, 0–2, 0–5, 1–5, 0–10V DC | |||||||||||||||
CONTROL OUTPUT | Y1- | Contact: Proportional Cycle 0.5–120.0 sec. Contact capacity: 240V AC 2.5A / resistive load |
||||||||||||||
I1- | Current: 4–20, 0–10mA DC Load resistance: 600Ω max. | |||||||||||||||
P1- | SSR drive voltage: Proportional Cycle 0.5–120.0 sec. Output rating: 15V±3V DC / 20mA max. |
|||||||||||||||
V1- | Voltage: 0–10V DC Load current: 2mA max. |
|||||||||||||||
PROGRAM FUNCTION (OPTION) | N | None | ||||||||||||||
P | 1 Pattern, 9 step | |||||||||||||||
EVENT OUTPUT (OPTION) | 0 | None | ||||||||||||||
1 | Contact (1a common): 240V AC 1A / resistive load EV1, EV2, EV3 / 3 Point | |||||||||||||||
REMOTE OR DI INPUT (OPTION) | 00 | None | ||||||||||||||
04 | 4–20mA DC Receiving resistance: 250Ω | |||||||||||||||
05 | 1– 5V DC Input resistance: 500kΩ min. | |||||||||||||||
06 | 0–10V DC Input resistance: 500kΩ min. | |||||||||||||||
51 | DI Non-Voltage Contact, Open Collector Input | |||||||||||||||
ANALOG OUTPUT OR COMMUNICATION FUNCTION (OPTION) |
00 | None | ||||||||||||||
03 | Voltage 0–10mV DC, Output resistance: 10Ω | |||||||||||||||
04 | Current 4–20mA DC, Load resistance: 300Ω max. | |||||||||||||||
06 | Voltage 0–10V DC, Load current: 1mA max. | |||||||||||||||
15 | RS-485 | |||||||||||||||
17 | RS-232C | |||||||||||||||
REMARKS | 0 | Without | ||||||||||||||
9 | With (Please consult before ordering.) |