Chromalox CTS Series Commercial Heat Trace Electronic Thermostat

Features

  • User Selectable Soft-Start Program
  • Small Enclosure. The 6.25-inch by 6.25-inch enclosure houses the temperature control and monitoring unit along with terminals for connecting instrument power, heating cable, and RTD.
  • 100 Ohm platinum RTD which can be pipe mounted or can be used to sense ambient air temperature.
  • Pipe stand-off mounts for direct pipe mounting.
  • Integral wiring. The wiring of the heating cable, alarm, AC power line, and the RTD sensor are all accomplished within the enclosure. This feature reduces both labor and material costs by eliminating the need for an additional heat trace power connection kit as well as the time for the additional wiring.
Enquiry

The CTS electronic thermostat is microprocessor-based temperature control and power connection kit. It is used for freeze protection or process temperature maintenance of pipes or tanks protected by heat tracing products. This thermostat can be used with CZH, CMi, or CPR heating cables in Ordinary area locations. This unit is designed to provide local temperature control and monitoring for heat traced pipes or tanks across a variety of industries and applications and will switch 30 amperes of current.

The CTS provides easy programming of the temperature setpoint, high and low-temperature alarms, the deadband, the temperature units, the soft-start function, and the alarm state through the front panel push buttons. A 9V battery connector is supplied to allow programming of the controller before heating cable circuit power is provided. LED lights are provided for indication of power to the unit, heater power on (load), and alarm status. A Fail-Safe solid-state alarm is included for wiring to your building management system to indicate alarm status. This alarm may be set to open or close on all alarm conditions including loss of power, high or low temperature alarm, and RTD failure. Choose either the DC or the AC customer-supplied voltage alarm variation. The minimum operating ambient temperature is -40°F (-40°C). This unit has programmable high and low-temperature alarm set points from -80°F (-62°C) to 1150°F (621°C).

The CTS employs a Soft Start feature that uses a proprietary software algorithm which reduces the inherent self-regulating in-rush current, resulting in less nuisance tripping at cold temperatures. For added flexibility, the user may disable the soft-start feature. A 100 Ohm platinum RTD is provided with a 3 foot (1 M) lead resulting in flexible mounting options for the user.

  • 30 Amp Solid State Relay (SSR) Output
  • 120 to 277 Vac Operation
  • cULus Ordinary Area and C1D2 Approval
  • On/Off Control with 100˚ Deadband Programmable in One Degree Increments
  • Selectable Soft-Start Feature
  • LED Indication for Power, Alarm, and Load
  • Large LED Display
  • Programmable High & Low-Temperature Alarms
  • 9V Battery Connector
  • Solid State Alarm for Remote Indication of Alarm Status–- ACAlarm: CTS- DCAlarm: CTS-DC
  • NEMA4X Enclosure
  • Integral Pipe Stand or Optional Wall Mount
  • 100 Ohm 3ft Platinum RTDIncluded
  • Enclosure Serves as Heating Cable, A/C Power & Sensor Connection
  • Works with CPR, CZH, and CMi Cable
  • RoHS Compliant
  • UL, cUL Listed

Dimension

Applications

  • Freeze Protection of Piping
  • Hot Water Temperature Maintenance
  • Tank Freeze Protection
  • Grease Waste Flow Maintenance

Specification

Operating Voltage 120 to 277 VAC, 50/60 Hz, Single Phase
Operating Temperature -40°F to 140°F (-40°C to 60°C
Input 100 Ohm platinum RTD
Output 30 amp solid state relay
Alarms High temp to 1150°F (621°C)
Low temp to -80°F (-62°C)
RTD Failure
Red LED alarm status indicator on front panel
Solid State Alarm Rating – AC 12-277 VAC, 1.8 Amps RMS – Customer Supplied
Solid State Alarm Rating – DC 0-42 VDC, 1.8 Amps RMS- Customer Supplied
Alarm Function Mode Default Optional
Normal Operation Closed Open
Alarm Condition Open Closed
Power Off Open Open
Deadband 1°F (or ˚C) to 100°F (or ˚C), programmable
Set Points -80°F to 1100°F programmable (-62˚C to 593˚C)
Units of Temperature ˚F or ˚C, selectable
Control Mode On/Off control
Soft Start User selectable integral soft start, patent pending    software algorithm, which eliminates nuisance breaker    tripping associated with self-regulating cable in-rush