ACI Platinum RTD Duct Without Box

Features

  • 1/4″ diameter stainless steel sensing element with two, 14 or 24 inch, 22 AWG Etched Teflon colored lead wires
  • The three-wire “-3W” option should be ordered if using with a 3-Wire temperature transmitter or sensor configuration on your building management system or PLC (Programmable Logic Controller).
  • Designed to be used in smaller duct applications and includes an insulation pad for properly sealing your duct as well as to dampen vibration.
  • Sensor length determined by the actual width or diameter of your duct
  • On larger ducts, you may want to refer to our Rigid or Bendable Copper Averaging sensor for increased sensing points and better temperature control.
  • The Duct without Box Series can be ordered with optional plenum rated cables, jacket materials and standard lead lengths.
Enquiry

Automation Components, Inc. (ACI) creates, manufactures, and distributes building automation sensors for the heating, ventilation, and air conditioning (HVAC) Industry. Dpstar is ACI Authorised Distributor in Malaysia. Our product lines include Temperature Sensors, Relative Humidity Sensors, Current Sensors, Pressure Sensors, Gas Sensors, and Wireless Sensors.

The ACI Platinum Duct without Box Series features a 1/4″ diameter stainless steel sensing element with two, 14 or 24 inch, 22 AWG Etched Teflon colored lead wires to differentiate the different sensor types. The three-wire “-3W” option should be ordered if using with a 3-Wire temperature transmitter or sensor configuration on your building management system or PLC (Programmable Logic Controller). The purpose of the 3rd wire is to compensate for any external lead wire resistance that will affect the accuracy of your sensors output signal. ACI recommends the use of 18 AWG lead wires to reduce the external lead wire resistance when using a Platinum RTD sensor and its lower sensor resolution. The sensors in this series are manufactured using ACI’s proven double encapsulation process to eliminate the effects of moisture upon the sensors as well as increased response times using our high quality, thermally conductive epoxy. The duct style sensor is a single point sensor designed to be used in smaller duct applications and includes an insulation pad for properly sealing your duct as well as to dampen vibration. Sensor length should be determined by the actual width or diameter of your duct such that the tip of the probe is in the approximate center of the duct. On larger ducts, you may want to refer to our Rigid or Bendable Copper Averaging sensor for increased sensing points and better temperature control. The Duct without Box Series can be ordered with optional plenum rated cables, jacket materials and standard lead lengths.

Dimension

Applications

  • Roof Top Units
  • Air Handlers
  • Monitoring Supply/Discharge/Return/Mixed Air Temperatures

The ACI Platinum RTD Duct Without Box Series is covered by ACI’s Five (5) Year Limited Warranty.

Specification

Sensor Type | Sensor Curve Platinum RTD | PTC (Positive Temperature Coefficient)
Number Sensing Points One
Number Wires A/100-2W-DO Series and A/1K-2W-DO Series: Two (Non-Polarity Sensitive)
A/100-3W-DO Series and A/1K-3W-DO Series: Three (Polarity Sensitive)
Sensor Output @ 0ºC (32ºF) A/100-xW-DO Series: 100 Ohms nominal | A/1K-xW-DO Series: 1000 Ohms nominal
Sensor Accuracy @ 0ºC (32ºF) +/- 0.06% Class A (Tolerance Formula: +/- ºC = (0.15ºC + (0.002 * |t|))
where |t| is the absolute value of Temperature above or below 0ºC in ºC)
-40ºC (-40ºF): +/- 0.23ºC (+/- 0.414ºF) | 0ºC (32ºF): +/- 0.15ºC (+/- 0.27ºF)
115ºC (239ºF): +/- 0.38ºC (+/- 0.69ºF)
Din Standard | Temperature Coe cient DIN EN 60751(IEC 751) | 3850 ppm / ºC
Sensor Stability +/- 0.03% after 1000 Hours @ 300ºC (572ºF)
Response Time (63% Step Change) 8 Seconds nominal
Self-Heating | Maximum Operating Current 100 Ohm RTD: 7 mW/ºC (Still Air) | 5 mA | 1K Ohm RTD: 4 mW/ºC (Still Air) | 3 mA
Operating | Storage Temperature Range -40 to 115ºC (-40 to 239ºF) | -40 to 85ºC (-40 to 185ºF)
Operating Humidity Range 10 to 95% RH, non-condensing
Probe Material | Flange Material 304 Stainless Steel | Galvanized Steel
Fitting Material | Flammability Rating Polyamide 66 (High Performance Nylon) | UL94-HB
Foam Pad Material | Flammability Rating Neoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C
Lead Length | Conductor Size 4”, 6” and 8” Probes: 14” (35.6 cm) | 12” and 18” Probes: 24” (61cm) | 22 AWG (0.65mm)
Lead Wire Insulation | Wire Rating Etched Te on (PTFE) Colored Leads | MIL-W-16878/4 (Type E)
Conductor Material Silver Plated Copper
Probe Diameter 0.250” (6.35mm)
Product Dimensions | Product Weight See table on back of Product Data sheet
Agency Approvals CE, RoHS2, WEEE

Download

ACI Platinum RTD Duct Without Box_DpstarGroup