ACI Platinum RTD Duct

Features

  • Stainless steel probe with Etched Teflon colored lead wires
  • The three-wire “-3W” option should be ordered when using with a 3-Wire temperature transmitter or sensor configuration on your building management system or PLC (Programmable Logic Controller).
  • The duct style sensor is a single point sensor designed to be used in smaller duct applications and includes an insulation pad for sealing the duct and dampening vibration.
  • The sensor length determined by the width or diameter of your duct, such that the tip of the probe is in the approximate center of the duct.
  • Standard enclosure options include the “-GD” Galvanized or “-PB” plastic enclosure with hinged cover.
  • On larger ducts, our Rigid or Bendable Copper Averaging sensor may offer better coverage based upon the size of your duct system and sensor location.
  • Optional NEMA/IP rated weather proof enclosures and NIST Certificates are available as referenced in the ordering grid.
Enquiry
Category:

Automation Components, Inc. (ACI) creates, manufactures, and distributes building automation sensors for the heating, ventilation, and air conditioning (HVAC) Industry. Dpstar is ACI Authorised Distributor in Malaysia. Our product lines include Temperature Sensors, Relative Humidity Sensors, Current Sensors, Pressure Sensors, Gas Sensors, and Wireless Sensors.

The ACI Platinum Duct Series features a stainless steel probe with Etched Teflon colored lead wires to differentiate the different sensor types. The three-wire “-3W” option should be ordered when using with a 3-Wire temperature transmitter or sensor configuration on your building management system or PLC (Programmable Logic Controller). The purpose of the 3rd wire is to compensate for external lead wire resistance that will affect the accuracy of your sensor output. ACI recommends the use of an 18 AWG lead wires to reduce the external lead wire resistance when using a Platinum RTD. The sensors are manufactured using ACI’s proven double encapsulation process to eliminate the effects of moisture on the sensors and to increase response times using our high quality, thermally conductive epoxy. The duct style sensor is a single point sensor designed to be used in smaller duct applications and includes an insulation pad for sealing the duct and dampening vibration. The sensor length should be determined by the width or diameter of your duct, such that the tip of the probe is in the approximate center of the duct. Standard enclosure options include the “-GD” Galvanized or “-PB” plastic enclosure with hinged cover. On larger ducts, our Rigid or Bendable Copper Averaging sensor may oer better coverage based upon the size of your duct system and sensor location. Optional NEMA/IP rated weather proof enclosures and NIST Certicates are available as referenced in the ordering grid.

Applications

  • Roof Top Units
  • Air Handlers
  • Monitoring Supply/Discharge/Return/Mixed Air Temperatures

The ACI Platinum RTD Duct Series is covered by ACI’s Five (5) Year Limited Warranty.

Specification

Sensor Type | Sensor Curve Platinum RTD | PTC (Positive Temperature Coe cient)
Number Sensing Points One
Number Wires A/100-2W-D Series and A/1K-2W-D Series: Two (Non-Polarity Sensitive)
A/100-3W-D Series and A/1K-3W-D Series: Three (Polarity Sensitive)
Sensor Output @ 0ºC (32ºF) A/100-xW-D Series: 100 Ohms nominal | A/1K-xW-D Series: 1000 Ohms nominal +/- 0.06% Class A (Tolerance Formula: +/- ºC = (0.15ºC + (0.002 * |t|)) where |t| is the absolute value of Temperature above or below 0ºC in ºC)
Sensor Accuracy @ 0ºC (32ºF) -40ºC (-40ºF): +/- 0.23ºC (+/- 0.414ºF) | 0ºC (32ºF): +/- 0.15ºC (+/- 0.27ºF)
115ºC (239ºF): +/- 0.38ºC (+/- 0.69ºF)
Din Standard | Temperature Coeffcient DIN EN 60751 (IEC 751) | 3850 ppm / ºC
Sensor Stability +/- 0.03% after 1000 Hours @ 300ºC (572ºF)
Response Time (63% Step Change) 8 Seconds nominal
Self-Heating | Maximum Operating Current 100 Ohm RTD: 7 mW/ºC (Still Air) | 5 mA | 1K Ohm RTD: 4 mW/ºC (Still Air) | 3 mA
Enclosure Speci cations (Operating Temperature
Range, Material, Flammability, NEMA/IP Ratings)
“-GD” Enclosure: -40 to 115ºC (-40 to 239ºF); Galvanized Steel; NEMA 1 (IP10)
“-PB” Enclosure: -30 to 90ºC (-22 to 194ºF); ABS Plastic; UL94-HB; Plenum Rated
“-BB” Enclosure: Aluminum, -40 to 121ºC (-40 to 250ºF), Plenum Rated, NEMA 3R
“-4X” Enclosure: -40 to 70ºC (-40 to 158ºF); Polystyrene Plastic; UL94-V2; NEMA 4X (IP 66)
Storage Temperature Range -40 to 85ºC (-40 to 185ºF)
Sensor Operating Temperature Range 40 to 392ºF (-40 to 200ºC)
Operating Humidity Range 10 to 95% RH, non-condensing
Probe Material 304 Stainless Steel
Fitting Material | Flammability Rating Polyamide 66 (High Performance Nylon) | UL94-HB
Foam Pad Material | Flammability Rating Neoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C
Lead Length | Conductor Size 4”, 6” & 8” Sensors: 14” (35.6cm) | 12” or 18” Sensors: 24” (61cm) | 22 AWG (0.65mm)
Lead Wire Insulation | Wire Rating Etched Te on (PTFE) Colored Leads | Mil Spec 16878/4 Type E)
Conductor Material Silver Plated Copper
Product Dimensions | Product Weight See table on back of Product Data sheet
Probe Diameter 0.250” (6.35mm)
Agency Approvals CE, RoHS2, WEEE

Download

ACI Platinum RTD Duct_DpstarGroup

Reviews

There are no reviews yet.

Be the first to review “ACI Platinum RTD Duct”