ENVIRONMENTAL CONDITIONS |
Operating temperature |
-40°C to +85°C |
Storage temperature |
-40°C to +85°C |
Calibration temperature |
20…28°C |
Relative humidity |
< 95% RH (non-cond.) |
Protection degree |
IP20 |
MECHANICAL SPECIFICATIONS |
Dimensions (HxWxD) |
109 x 23.5 x 104 mm |
Weight (1 / 2 channels) |
145 / 185 g |
DIN rail type |
DIN EN 60715/35 mm |
Wire size |
0.13…2.08 mm2 AWG 26…14 stranded wire |
Screw terminal torque |
0.5 Nm |
COMMON SPECIFICATIONS |
Supply |
|
Supply voltage |
7.2…35 VDC |
Power dissipation, per channel |
0.17…0.8 W |
Isolation voltage |
|
Isolation voltage, test / working |
1.5 kVAC / 50 VAC |
Response time |
|
Response time (programmable) |
1…60 s |
Voltage drop |
7.2 VDC |
Warm-up time |
5 min. |
Programming |
Loop Link |
Signal / noise ratio |
Min. 60 dB |
Accuracy |
Better than 0.05% of selected range |
EEprom error check |
< 3.5 s |
Signal dynamics, input |
20 bit |
Signal dynamics, output |
16 bit |
Effect of supply voltage change |
< 0.005% of span / VDC |
EMC immunity influence |
< ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst |
< ±1% of span |
INPUT SPECIFICATIONS |
Common input specifications |
|
Max. offset |
50% of selected max. value |
RTD input |
|
RTD type |
Pt100, Ni100, lin. R |
Cable resistance per wire |
5 Ω (max.) |
Sensor current |
Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) |
< 0.002 Ω / Ω |
Sensor error detection |
Yes |
TC input |
|
Thermocouple type |
B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) |
< ±1.0°C |
Sensor error detection |
Yes |
Sensor error current: When detecting / else |
Nom. 33 μA / 0 μA |
Linear resistance input |
|
Linear resistance min….max. |
0 Ω…5000 Ω |
Voltage input |
|
Measurement range |
-12…800 mV |
Min. measurement range (span) |
5 mV |
Input resistance |
10 MΩ |
OUTPUT SPECIFICATIONS |
Current output |
|
Signal range |
4…20 mA |
Min. signal range |
16 mA |
Load (@ current output) |
≤ (Vsupply – 7.2) / 0.023 [Ω] |
Load stability |
≤ 0.01% of span / 100 Ω |
Sensor error indication |
Programmable 3.5…23 mA |
NAMUR NE43 Upscale/Downscale |
23 mA / 3.5 mA |
Common output specifications |
|
Updating time |
440 ms |
of span |
= of the presently selected range |
OBSERVED AUTHORITY REQUIREMENTS |
EMC |
2014/30/EU |
EAC |
TR-CU 020/2011 |
APPROVALS |
ATEX |
KEMA 10ATEX0005 X |
IECEx |
DEK 14.0047 X |
EAC Ex |
RU C-DK.HA65.B.00355/19 |
Reviews
There are no reviews yet.